SVO224OUC3: Long Piping & Height Difference
- The total pipe length: 100m
- Cooling operating temperature range is from -5˚C to +50˚C. Heating operating temperature range is from -20 ˚C to +30 ˚C.
- The longest pipe:
Actual length 60m
Equivalent length 70m - Equivalent length from first indoor distributor to last indoor unit: 20m
- Height deference between indoor and outdoor unit:
Outdoor unit above <30m
Outdoor unit below <20m - Height difference between indoor units: 8m
Specification
Model name |
Power type |
Cooling |
Heating |
Compresor |
Motor |
Refrigerant |
SoundpresureLevel |
SoundpowerLevel |
Dimension(WxHxD) |
Weight |
Connecting |
Max.Connectedindoor unitsquantity |
||||||||||||||
Capacity |
Power input |
Current |
EER |
Capacity |
Power input |
Current |
COP |
Type |
Quantity |
Type |
Quantity |
Type |
Volume |
Packing |
Body |
Net |
Gross |
Gas |
Liquid |
|||||||
kW |
Btu/h |
kW |
A |
kW |
Btu/h |
kW |
A |
kg |
dB(A) |
dB(A) |
mm |
mm |
kg |
kg |
mm |
mm |
||||||||||
SVO224OUC3 |
380-415V-3ph-5ohz
|
22.4 |
76500 |
6.74
|
10.5
|
3.32 |
25
|
85300
|
5.85
|
9.9
|
4.27
|
DC/Twin-
|
1
|
DCfan
|
2
|
R410a
|
6.1 |
45-58 |
52-65 |
1278x1696x560
|
1120x1549x400
|
145
|
165
|
Φ22.2
|
Φ9.53 |
10 |